Moxa ioLogik E2210 [201/263] Iologik e2200 series modbus tcp address mappings

Moxa ioLogik E2262 [201/263] Iologik e2200 series modbus tcp address mappings
ioLogik E2200 Series Modbus/TCP Address Mappings
I-27
Reference Address Data Type Description
40077 0x004C word CH4 DI mode
0: DI
1: count
Other: return illegal data value
40078 0x004D word CH5 DI mode
0: DI
1: count
Other: return illegal data value
40079 0x004E word CH6 DI mode
0: DI
1: count
Other: return illegal data value
40080 0x004F word CH7 DI mode
0: DI
1: count
Other: return illegal data value
40081 0x0050 word CH8 DI mode
0: DI
1: count
Other: return illegal data value
40082 0x0051 word CH9 DI mode
0: DI
1: count
Other: return illegal data value
40083 0x0052 word CH10 DI mode
0: DI
1: count
Other: return illegal data value
40084 0x0053 word CH11 DI mode
0: DI
1: count
Other: return illegal data value
For Citect SCADA compatibility, I/O data can be WORD accessed as well
40085 0x0054 1 word CH0 DO value
0: off 1: on
40086 0x0055 1 word CH1 DO value
0: off 1: on
40087 0x0056 1 word CH2 DO value
0: off 1: on
40088 0x0057 1 word CH3 DO value
0: off 1: on
40089 0x0058 1 word CH4 DO value
0: off 1: on
40090 0x0059 1 word CH5 DO value
0: off 1: on
40091 0x005A 1 word CH6 DO value
0: off 1: on
40092 0x005B 1 word CH7 DO value
0: off 1: on
40093 0x005C 1 word CH8 DO value
0: off 1: on
40094 0x005D 1 word CH9 DO value
0: off 1: on