After clicking the Test tab, you can see how a channel’s status affects or is affected by the attached device. For
DO channels, you can set the ON/OFF status or START/STOP pulse output. For DI channels, you can monitor
the attached devices’ ON/OFF status, or monitor the counter.
You can now use ioAdmin to set up or configure your ioLogik E2200. For additional information on using
ioAdmin, see Chapter 3.
Adding More I/O Channels
A cost-effective way to add more I/O channels to your ioLogik is to attach an appropriate ioLogik R2140. The
2 ioLogiks can be snapped together using the RS-485 system bus connector. For the ioLogik E2200 series,
additional analog channels can be added by using the ioLogik R2140.
ATTENTION
Multiple ioLogik E2200/R21
40 units can be snapped together as part of the same RS-
485 network. But when
connecting the power, be sure to use the following steps in the order below:
1.
Remove the cover from the male system bus connector on the first ioLogik’s right side panel
2.
Remove the cover from the female system bus connector on the second ioLogik’s left side panel
3.
Insert the first ioLogik’s male system bus connector into the second ioLogik’s female system bus connector
4.
Replace the covers on the exposed system bus connectors
5.
Turn on the system power
ATTENTION
A total of 31 additional ioLogik R21
40 products can be attached to one ioLogik E2200. The best space-
saving
arrangement is to use the TB1 terminal block for the cascaded RS
-
485 connections, instead of using the system
bus.