ioLogik E2200 Series Modbus/TCP Address Mappings
I-79
Reference Address Data Type Description
40033 0x0020 1 word CH4 RTD Engineering Unit
40034 0x0021 1 word CH5 RTD Engineering Unit
40035 0x0022 1 word Virtual CH6 RTD Engineering Unit
1=Celsius, 2=Fahrenheit
40036 0x0023 1 word Virtual CH7 RTD Engineering Unit
40037 0x0024 1 word Virtual CH8 RTD Engineering Unit
40038 0x0025 1 word Virtual CH9 RTD Engineering Unit
40039 0x0026 1 word Virtual CH10 RTD Engineering Unit
40040 0x0027 1 word Virtual CH11 RTD Engineering Unit
40041 0x0028 1 word CH0 RTD Sensor Type
0=PT50
1=PT100
2=PT200
3=PT500
4=PT1000
5=JPT100
6=JPT200
7=JPT500
8=JPT1000
9=NI100
10=NI200
11=NI500
12=NI1000
13=NI120
14=310 Ohm
15=620 Ohm
16=1250 Ohm
17=2500 Ohm
40042 0x0029 1 word CH1 RTD Sensor Type
40043 0x002A 1 word CH2 RTD Sensor Type
40044 0x002B 1 word CH3 RTD Sensor Type
40045 0x002C 1 word CH4 RTD Sensor Type
40046 0x002D 1 word CH5 RTD Sensor Type
40047 0x002E 1 word CH6 RTD Sensor Type
20=AVG
21=DIV
40048 0x002F 1 word Virtual CH7 RTD Sensor Type
40049 0x0030 1 word Virtual CH8 RTD Sensor Type
40050 0x0031 1 word Virtual CH9 RTD Sensor Type
40051 0x0032 1 word Virtual CH10 RTD Sensor Type
40052 0x0033 1 word Virtual CH11 RTD Sensor Type
40053 0x0034 1 word CH0 RTD Reset Minimum Value
<R> Always 0
<W> 1=Reset, 0=return illegal data value
40054 0x0035 1 word CH1 RTD Reset Minimum Value
40055 0x0036 1 word CH2 RTD Reset Minimum Value
40056 0x0037 1 word CH3 RTD Reset Minimum Value
40057 0x0038 1 word CH4 RTD Reset Minimum Value
40058 0x0039 1 word CH5 RTD Reset Minimum Value
40059 0x003A 1 word Virtual CH6 RTD Reset Minimum Value
40060 0x003B 1 word Virtual CH7 RTD Reset Minimum Value
40061 0x003C 1 word Virtual CH8 RTD Reset Minimum Value