Moxa ioLogik E2210 [92/263] Iologik e2200 series click go

Moxa ioLogik E2260 [92/263] Iologik e2200 series click go
ioLogik E2200 Series Click&Go
4-19
If Conditions
Result of
OR Logic
Trigger of
Then Actions
Trigger of
ELSE Actions
A1 A2 A3
0 0 0 0 NO YES
0 0 1 1 YES NO
0 1 0 1 YES NO
0 1 1 1 YES NO
1 0 0 1 YES NO
1 0 1 1 YES NO
1 1 0 1 YES NO
1 1 1 1 YES NO
THEN/ELSE actions can be specified as follows:
THEN/ELSE
Actions
Operators Remark
Counter RESET Counter-x represents the number of the
Event Counter channel
DO ON, OFF DO-x represents the number of the channel.
Pulse Output STOP, START Pulse Output-x represents the number of the channel
AO Built-in or Expansion
Relay RESET ResetCNT-x represents the number of the relay channel.
Internal
Register
Reg-x represents the number of the internal register.
x = 00 to 23 / Trigger Value: 0 to 255
Timer STOP, START,
RESTART
Timer-x, x = 00 to 23
Max value: 4,294,967 seconds
SNMP Trap I/O Status Bindings: 3 sets
Active Message ID / Source IP Unicode supported
e-Mail Create the contents of the e-Mail
Short Message
Service
Select recipients from the phone book, define the content, and configure
the escalation
Data Log
Start/Stop
Start, Stop Select which profile to start or stop
FTP Service Select which profile and FTP server to upload the log file
NOTE
T
he following THEN Actions are only supported by ioLogik W5300 Cellular Remote IO devices:
Short Message
Service
, Data Log Start/Stop, and FTP Service.