Moxa ioLogik E2210 [204/263] Iologik e2200 series modbus tcp address mappings

Moxa ioLogik E2212-T [204/263] Iologik e2200 series modbus tcp address mappings
ioLogik E2200 Series Modbus/TCP Address Mappings
I-30
Reference Address Data Type Description
40147 0x0092 1 word CH2 DO safe mode pulse operate status
0: stop 1: start
40148 0x0093 1 word CH3 DO safe mode pulse operate status
0: stop 1: start
40149 0x0094 1 word CH4 DO safe mode pulse operate status
0: stop 1: start
40150 0x0095 1 word CH5 DO safe mode pulse operate status
0: stop 1: start
40151 0x0096 1 word CH6 DO safe mode pulse operate status
0: stop 1: start
40152 0x0097 1 word CH7 DO safe mode pulse operate status
0: stop 1: start
40153 0x0098 1 word CH8 DO safe mode pulse operate status
0: stop 1: start
40154 0x0099 1 word CH9 DO safe mode pulse operate status
0: stop 1: start
40155 0x009A 1 word CH10 DO safe mode pulse operate status
0: stop 1: start
40156 0x009B 1 word CH11 DO safe mode pulse operate status
0: stop 1: start
40157 0x009C 1 word CH0 DI counter operate status
0: stop 1: start
40158 0x009D 1 word CH1 DI counter operate status
0: stop 1: start
40159 0x009E 1 word CH2 DI counter operate status
0: stop 1: start
40160 0x009F 1 word CH3 DI counter operate status
0: stop 1: start
40161 0x0A0 1 word CH4 DI counter operate status
0: stop 1: start
40162 0x00A1 1 word CH5 DI counter operate status
0: stop 1: start
40163 0x00A2 1 word CH6 DI counter operate status
0: stop 1: start
40164 0x00A3 1 word CH7 DI counter operate status
0: stop 1: start
40165 0x00A4 1 word CH8 DI counter operate status
0: stop 1: start
40166 0x00A5 1 word CH9 DI counter operate status
0: stop 1: start
40167 0x00A6 1 word CH10 DI counter operate status
0: stop 1: start
40168 0x00A7 1 word CH11 DI counter operate status
0: stop 1: start
40169 0x00A8 1 word CH0 DI clear count value
Read:
0: no action
Write:
1: clear counter value
0: return illegal data value(0x03)