Configuring Digital Output / Relay Output Channels
The ioLogik E2200 series digital output and relay output channels can be set to “DO” or “Pulse Output” mode.
In DO mode, the specifications are as follows.
Type OFF ON
DO mode Open Short
In Pulse Output mode, the selected digital output channel will generate a square wave as specified in the
pulse mode parameters. The low and high level widths are specified in multiples of 0.5 ms for Digital Output
(1.5 s for Relay output), with a maximum setting of 65,535. For digital output, you would enter 1000 for a width
of 500 ms. If the OFF width value is 5000 and the ON width value is 5000, the pulse output would be a square
wave with a 5-second pulse cycle. You can specify between 1 and 4,294,967,295 pulses or enter “0” for
continuous pulse output.
When the ioLogik is first powered on, the status of each DO channel is be set to “OFF” by default. This behavior
can be modified using the Power On Settings. You can set a DO channel to turn “ON” when the ioLogik is
powered on, or to commence pulse output.