Moxa ioLogik E2210 [177/263] Iologik e2200 series modbus tcp address mappings

Moxa ioLogik E2214 [177/263] Iologik e2200 series modbus tcp address mappings
ioLogik E2200 Series Modbus/TCP Address Mappings
I-3
Reference Address Data Type Description
00047 0x002E 1 bit CH6 DO Pulse Safe Mode Status 0: Off 1: On
00048 0x002F 1 bit CH7 DO Pulse Safe Mode Status 0: Off 1: On
00049 0x0030 1 bit CH0 DI Counter Status 0: Stop 1: Start
00050 0x0031 1 bit CH1 DI Counter Status 0: Stop 1: Start
00051 0x0032 1 bit CH2 DI Counter Status 0: Stop 1: Start
00052 0x0033 1 bit CH3 DI Counter Status 0: Stop 1: Start
00053 0x0034 1 bit CH4 DI Counter Status 0: Stop 1: Start
00054 0x0035 1 bit CH5 DI Counter Status 0: Stop 1: Start
00055 0x0036 1 bit CH6 DI Counter Status 0: Stop 1: Start
00056 0x0037 1 bit CH7 DI Counter Status 0: Stop 1: Start
00057 0x0038 1 bit CH8 DI Counter Status 0: Stop 1: Start
00058 0x0039 1 bit CH9 DI Counter Status 0: Stop 1: Start
00059 0x003A 1 bit CH10 DI Counter Status 0: Stop 1: Start
00060 0x003B 1 bit CH11 DI Counter Status 0: Stop 1: Start
00061 0x003C 1 bit CH0 DI Clear Counter Value
Read: Always 0
Write: 1 : Clear Counter Value
0 : Return Illegal Data Value
00062 0x003D 1 bit CH1 DI Clear Counter Value
Read: Always 0
Write: 1 : Clear Counter Value
0 : Return Illegal Data Value
00063 0x003E 1 bit CH2 DI Clear Counter Value
Read: Always 0
Write: 1 : Clear Counter Value
0 : Return Illegal Data Value
00064 0x003F 1 bit CH3 DI Clear Counter Value
Read: Always 0
Write: 1 : Clear Counter Value
0 : Return Illegal Data Value
00065 0x0040 1 bit CH4 DI Clear Counter Value
Read: Always 0
Write: 1 : Clear Counter Value
0 : Return Illegal Data Value
00066 0x0041 1 bit CH5 DI Clear Counter Value
Read: Always 0
Write: 1 : Clear Counter Value
0 : Return Illegal Data Value
00067 0x0042 1 bit CH6 DI Clear Counter Value
Read: Always 0
Write: 1 : Clear Counter Value
0 : Return Illegal Data Value
00068 0x0043 1 bit CH7 DI Clear Counter Value
Read: Always 0
Write: 1 : Clear Counter Value
0 : Return Illegal Data Value
00069 0x0044 1 bit CH8 DI Clear Counter Value
Read: Always 0
Write: 1 : Clear Counter Value
0 : Return Illegal Data Value