Moxa ioLogik E2210 [129/263] Heartbeat interval

Moxa ioLogik E2214-T [129/263] Heartbeat interval
ioLogik E2200 Series Active OPC Server
6-11
Heartbeat Interval
Tags are event-driven and updated only when the status of an I/O channel changes, so when the status
remains unchanged, there an update will not be sent to Active OPC Server. To ensure that the ioLogik is
connected and alive, Heartbeat Interval can be used to determine the connection status between the ioLogik
and Active OPC Server. If the heartbeat interval is set and the network between the ioLogik and Active OPC
Server is down, Active OPC Server will detect the stop of the heartbeat and the Quality column will show BAD
to indicate the loss of the connection. The default interval is set to 0 seconds, which disables the heartbeat. The
maximum allowed interval is 65,535 seconds.
Read/Write Privilege
The R/W column shows whether a tag is read only, or provides both read and write access. The input channels
can be read, but cannot be written to, whereas the output channels can be both read and written to. Note that
if an output channel has been used by the Click&Go logic, the tags for that channel are read-only.

Содержание

Скачать
Случайные обсуждения

Ответы 1

Какие характеристики у ioLogik E2242?
2 года назад